Section 608RefrigerantPrep

Free sheet · print this

The 608 fact sheet

Every number below is drawn from 40 CFR Part 82 Subpart F as published.

The exam

Structure25 Core + 25 per type; Universal 100
Passing70% closed-book; 84% mail-in Type I
Core coversEnvironmental impact of CFCs, HCFCs and substitutes; Laws and regulations; Changing industry outlook
Type sections coverLeak detection, Recovery techniques, Safety, Shipping, Disposal
ExpirationThe regulation sets no expiration or renewal requirement for technician certification.

The four certifications

TypeCovers
Type ISmall appliances: factory-sealed units holding 5 pounds of refrigerant or less
Type IIMedium-, high- and very high-pressure appliances, the residential and commercial split-system world
Type IIILow-pressure appliances, the chiller plant world
UniversalAll three types

The numbers the exam asks for

RuleFigure
Leak rate, commercial refrigeration (50 lb+)20%
Leak rate, industrial process refrigeration30%
Leak rate, comfort cooling and other 50 lb+10%
Chronic-leak report to EPA125% of full charge in a calendar year
Purge exclusion, verified destruction98%+
Small-appliance recovery, pre-11/15/1993 equipment80%
Later equipment, compressor running / not running90% / 80%
Small-appliance evacuation alternative4 in Hg vacuum
MVAC disposal102 mm Hg vacuum
Record retention3 years minimum
Servicing records required at50 lb or more
Small appliance definition5 lb or less, factory sealed

refrigerantprep.com · figures per 40 CFR Part 82 Subpart F as published · independent material, confirm current requirements with your certifying organization.